SWA Cable - power and auxiliary control cables for use in power networks, underground, outdoor and indoor applications and for use in cable ducting.
Voltage Rating Uo/U 0.6/1kV
APPLICATION
The N2XFGbY cable is suitable for installation in the ground, indoors, cable trunking and outdoors if increased mechanical protection is required where high-pulling stresses may occur during installation or operation offering.
CONSTRUCTION
Conductor
Class 2 Stranded copper
Insulation
XLPE (Cross-Linked Polyethylene)
Filler
PVC (Polyvinyl chloride)
Armour 1
SWA (Galvanised flat steel wire)
Armour 2
Galvanised steel tape
Outer Sheath
PVC (Polyvinyl chloride)
Core Identification
2core: Blue Brown
3core: Brown Black Grey
4core: Blue Brown Black Grey
5core: Blue Brown Black Grey Black
Outer Sheath Colour
Black
STANDARDS
IEC 60502-1, VDE 0276-603
Flame retardant according to IEC 60332-1
DIMENSIONS | |||||||||||||||
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm² | NOMINAL DIAMETER OF CONDUCTOR mm | NOMINAL THICKNESS OF INSULATION mm | NOMINAL THICKNESS OF OUTER SHEATH mm | NOMINAL OVERALL DIAMETER mm | NOMINAL WEIGHT kg/km | |||||||||
3 | 10 | 3.9 | 0.7 | 1.24 | 19 | 922 | |||||||||
3 | 16 | 4.8 | 0.7 | 1.24 | 21 | 1186 | |||||||||
3 | 25 | 5.9 | 0.9 | 1.24 | 24 | 1655 | |||||||||
3 | 35 | 6.9 | 0.9 | 1.32 | 27 | 2100 | |||||||||
3 | 50 | 8.2 | 1 | 1.4 | 31 | 2724 | |||||||||
3 | 70 | 9.7 | 1.1 | 1.48 | 35 | 3608 | |||||||||
3 | 95 | 11.4 | 1.1 | 1.64 | 39 | 4637 | |||||||||
3 | 120 | 13.1 | 1.2 | 1.72 | 44 | 5701 | |||||||||
3 | 150 | 14.2 | 1.4 | 1.88 | 47 | 6779 | |||||||||
3 | 185 | 15.8 | 1.6 | 2.04 | 53 | 8437 | |||||||||
3 | 240 | 18.6 | 1.7 | 2.2 | 60 | 10889 | |||||||||
3 | 16/10 | 4.8 | 0.7 | 1.24 | 23 | 1372 | |||||||||
3 | 25/16 | 5.9 | 0.9 | 1.24 | 26 | 1890 | |||||||||
3 | 35/16 | 6.9 | 0.9 | 1.32 | 28 | 2286 | |||||||||
3 | 50/25 | 8.2 | 1 | 1.4 | 32 | 3017 | |||||||||
3 | 70/35 | 9.7 | 1.1 | 1.56 | 37 | 3990 | |||||||||
3 | 95/50 | 11.4 | 1.1 | 1.64 | 41 | 5160 | |||||||||
3 | 120/70 | 13.1 | 1.2 | 1.8 | 46 | 6428 | |||||||||
3 | 150/70 | 14.2 | 1.4 | 1.88 | 49 | 7525 | |||||||||
3 | 185/95 | 15.8 | 1.6 | 2.04 | 55 | 9429 | |||||||||
3 | 240/120 | 18.6 | 1.7 | 2.2 | 62 | 11956 | |||||||||
4 | 10 | 3.9 | 0.7 | 1.24 | 20 | 1071 | |||||||||
4 | 16 | 4.8 | 0.7 | 1.24 | 23 | 1400 | |||||||||
4 | 25 | 5.9 | 0.9 | 1.32 | 27 | 1985 | |||||||||
4 | 35 | 6.9 | 0.9 | 1.4 | 30 | 2530 | |||||||||
4 | 50 | 8.2 | 1 | 1.48 | 34 | 3299 | |||||||||
4 | 70 | 9.7 | 1.1 | 1.56 | 38 | 4398 | |||||||||
4 | 95 | 11.4 | 1.1 | 1.72 | 43 | 5693 | |||||||||
4 | 120 | 13.1 | 1.2 | 1.88 | 48 | 7041 | |||||||||
4 | 150 | 14.2 | 1.4 | 1.96 | 52 | 8495 | |||||||||
4 | 185 | 15.8 | 1.6 | 2.12 | 58 | 10564 | |||||||||
4 | 240 | 18.6 | 1.7 | 2.36 | 66 | 13684 | |||||||||
4 | 300 | 21.5 | 1.9 | 3.06 | 78 | 17628 | |||||||||
5 | 10 | 3.9 | 0.7 | 1.24 | 23 | 1342 | |||||||||
5 | 16 | 4.8 | 0.7 | 1.24 | 24 | 1715 | |||||||||
5 | 25 | 5.9 | 0.9 | 1.32 | 30 | 2536 | |||||||||
5 | 35 | 6.9 | 0.9 | 1.4 | 33 | 3209 | |||||||||
5 | 50 | 8.2 | 1 | 1.48 | 37 | 4192 |
ELECTRICAL CHARACTERISTICS | ||||||||||||||||
NOMINAL CROSS SECTIONAL AREA mm2 | CURRENT CARRYING CAPACITY A | MAXIMUM CONDUCTOR RESISTANCE AT 20°C Ω/km | ||||||||||||||
IN CONDUIT | IN AIR | |||||||||||||||
10 | 346 | 355 | 1.83 | |||||||||||||
16 | 390 | 407 | 1.15 | |||||||||||||
25 | 441 | 469 | 0.727 | |||||||||||||
35 | 511 | 551 | 0.524 | |||||||||||||
50 | 580 | 638 | 0.387 | |||||||||||||
70 | 86 | 73 | 0.268 | |||||||||||||
95 | 111 | 96 | 0.193 | |||||||||||||
120 | 143 | 130 | 0.153 | |||||||||||||
150 | 390 | 407 | 0.124 | |||||||||||||
185 | 441 | 469 | 0.0991 | |||||||||||||
240 | 511 | 551 | 0.0754 | |||||||||||||
300 | 580 | 638 | 0.0601 |