BS 6622 3.8/6.6kV Cable 24

CHARACTERISTICS

Voltage Rating Uo/U (Um) 3.8/6.6 (7.2) kV

Test Voltage (AC) 15kV

Temperature Rating

Maximum operating temperature: 90°C

Maximum short circuit temperature: 250°C

Minimum Bending Radius Single core: 15x overall diameter Multi core: 12 x overall diameter

(Single core 12 x overall diameter and 3 core 10 x overall diameter where bends are positioned adjacent to a joint or termination provided that the bending is carefully controlled by the use of a former)


Overview

APPLICATION

Armoured power distribution cables for external and direct burial applications in power networks.

CHARACTERISTICS

Voltage Rating Uo/U (Um) 3.8/6.6 (7.2) kV

Test Voltage (AC) 15kV

Temperature Rating

Maximum operating temperature: 90°C

Maximum short circuit temperature: 250°C

Minimum Bending Radius Single core: 15x overall diameter Multi core: 12 x overall diameter

(Single core 12 x overall diameter and 3 core 10 x overall diameter where bends are positioned adjacent to a joint or termination provided that the bending is carefully controlled by the use of a former)

CONSTRUCTION

Conductor: Class 2 stranded compacted copper conductor

Conductor Screen: Semi-conductive XLPE (Cross-Linked Polyethylene)

Insulation: XLPE (Cross-Linked Polyethylene)

Insulation Screen: Semi-conductive XLPE (Cross-Linked Polyethylene)

MetallicScreen: Concentric copper wires and copper tape

Separator: Binding tape

Inner Sheath: PVC (Polyvinyl Chloride)

Armour: 

Single core: AWA (Aluminium Wire) Multi core: SWA (Galvanised steel wire)

Sheath: PVC (Polyvinyl Chloride)

Sheath Colour: Red


Parameter

DIMENSIONS
ELECTRICAL CHARACTERISTICS
DIMENSIONS
NO. OF CORESNOMINAL CROSS SECTIONAL AREA
mm2
NOMINAL OVERALL DIAMETER
mm
NOMINAL WEIGHT
kg/ km
13524.301.023
15025.501.171
17027.301.418
19529.201.719
112031.102.013
115032.302.386
118535.002.866
124037.703.486
130041.704.256
140047.105.406
150051.906.693
163055.808.212
350484500
370525500
395566500
3120607500
3150638500
31856710000
32407413000
33008015500
34008919000
Expand More
ELECTRICAL CHARACTERISTICS
Single Core
NO. OF CORESNOMINAL CROSS
SECTIONAL AREA
mm2
MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC
ohms/ km
OPERATING INDUCTANCE
mH/ km
OPERATING CAPACITY
uF/ km
CONTINUOUS CURRENT RATING
Amps
FlatTrefoilIn Ground at 20OCIn Air at 30OC
FlatTrefoilFlatTrefoil
1350.5240.7480.4010.266201191238199
1500.3870.7190.3810.297241227285241
1700.2680.6840.3570.339301277356301
1950.1930.6590.3420.381364331435365
11200.1530.6360.3270.416424379496419
11500.1240.6200.3190.454479422554479
11850.09910.6020.3100.495549476637543
12400.07540.5790.3000.556595550746640
13000.06010.5620.2950.617626591831722
14000.04700.5430.2900.681675662920827
15000.03660.5250.2830.7587487441043949
16300.02830.5070.2760.85398185611801076
ELECTRICAL CHARACTERISTICS
Multi Core
NO. OF CORESNOMINAL CROSS SECTIONAL AREA
mm2
MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC
ohms/ km
OPERATING INDUCTANCE
mH/ km
OPERATING CAPACITY
uF/ km
CONTINUOUS CURRENT RATING
Amps
In Ground at 20OCIn Air at 30OC
3500.3870.330.30208196
3700.2680.310.35255249
3950.1930.290.39307307
31200.1530.280.43353353
31500.1240.280.47396406
31850.09910.270.51447464
32400.07540.260.55523548
33000.06010.260.57581632
34000.04700.260.59653726
32400.07540.260.55523548
33000.06010.260.57581632
34000.04700.260.59653726

Expand More