BS 6622 XLPE PVC 8.7/15kV Cable

CHARACTERISTICS

Voltage Rating Uo/U (Um)

8.7/15 (17.5) kV

Temperature Rating

Fixed: 0°C to +90°C

Minimum Bending Radius

Single core - Fixed: 15 x overall diameter 3 core - Fixed: 12 x overall diameter

(Single core 12 x overall diameter and 3 core 10 x overall diameter where bends are positioned adjacent to a joint or termination provided that the bending is carefully controlled by the use of a former)


Overview

BS 6622 XLPE PVC 8.7/15kV Cable


APPLICATION

Medium voltage PVC power cables for power networks, underground and in cable ducting.

CHARACTERISTICS

Voltage Rating Uo/U (Um)

8.7/15 (17.5) kV

Temperature Rating

Fixed: 0°C to +90°C

Minimum Bending Radius

Single core - Fixed: 15 x overall diameter 3 core - Fixed: 12 x overall diameter

(Single core 12 x overall diameter and 3 core 10 x overall diameter where bends are positioned adjacent to a joint or termination provided that the bending is carefully controlled by the use of a former)

CONSTRUCTION

Conductor

Class 2 stranded copper conductor

Conductor Screen

Semi-conductive XLPE (Cross-Linked Polyethylene)

Insulation

XLPE (Cross-Linked Polyethylene)

Insulation Screen

Semi-conductive XLPE (Cross-Linked Polyethylene)

Metallic Screen

Individual or collective overall copper tape screen

Filler

PET (Polyethylene Terephthalate) fibres

Separator

Binding tape

Bedding

PVC (Polyvinyl Chloride)

Armour

Single core: AWA (Aluminium Wire Armoured) Multi-core: SWA (Steel Wire Armoured)

Sheath

PVC (Polyvinyl Chloride)

Sheath Colour

Red     Black

STANDARDS

BS 6622, IEC/EN 60228 ,Flame Retardant according to IEC/EN 60332-1-2



Parameter

DIMENSIONS
CONDUCTORS
ELECTRICAL CHARACTERISTICS
DIMENSIONS
NUMBER OF CORESNOMINAL CROSS SECTIONAL AREA
mm2
MINIMUM THICKNESS
mm
NOMINAL THICKNESS OF SEMI CONDUCTIVE LAYER
mm
NOMINAL DIAMETER
mm
NOMINAL WEIGHT
kg/km
InsulationOuter sheathInnerOuterOver insulationOverall
1503.951.320.500.8019.50291400
1703.951.400.500.8021.10311700
1953.951.480.500.8022.80342100
11203.951.480.500.8024.10352350
11503.951.560.500.8026.00372700
11853.951.560.500.8027.30393200
12403.951.640.500.8030.00423750
13003.951.720.500.8032.10454600
14003.951.800.500.8035.00485500
15003.951.880.500.8038.00516750
16303.951.960.500.8042.10568200
3503.952.120.500.8019.50575500
3703.952.200.500.8021.10616500
3953.952.280.500.8022.80657600
31203.952.360.500.8024.10688600
31503.952.520.500.8026.007410500
31853.952.600.500.8027.307711900
32403.952.760.500.8030.008314200
33003.952.840.500.8032.108816600
34003.953.080.500.8035.009519700
35003.953.240.500.8038.0010323600
Expand More
CONDUCTORS
Class 2 Stranded Conductors for Single Core and Multi-Core Cables
NOMINAL CROSS SECTIONAL AREA
mm2
NOMINAL DIAMTER OF CONDUCTORNOMINAL SHORT CIRCUIT CURRENT AT 1 SECOND
kA
CONDUCTOR  DC RESISTANCE AT 20 °C
Ω/km
CONDUCTOR  DC RESISTANCE AT 20 °C
Ω/km
508.107.150.3870.497
709.7010.010.2680.344
9511.4013.590.1930.248
12012.7017.160.1530.196
15014.5021.450.1240.160
18515.9026.460.09910.128
24018.6034.320.07540.098
30020.7042.900.06010.080
40023.5057.200.04700.064
50026.5071.500.03660.0510
63030.2090.090.02830.0420
Expand More
ELECTRICAL CHARACTERISTICS
Current Carrying Capacity
NUMBER OF CORESNOMINAL CROSS SECTIONAL AREA
mm2
CURRENT CARRYING CAPACITY
A
CONDUCTOR LOSSES IN THE GROUND
kW/km
In ground (20 °C)In air (30 °C)
15024927730.81
17030334531.58
19535841831.78
112040448131.99
115044153731.12
118549361231.11
124056371631.06
130062681131.35
140067690129.25
1500743100628.15
1630---
35021020665.75
37025625767.63
39530731370.12
312034936071.62
315039241073.76
318544346975.36
324051355377.40
330057663579.60
340065073181.10
3500---
Expand More
Inquiry
We respond quickly to any questions, inquiries, needs and feedback. If you have business needs or questions about our products, feel free to contact us.
WhatsApp

WhatsApp

WeChat

WeChat