CONSTRUCTION
Conductor:Class 2 stranded copper conductor
Inner Semi-Conductive Layer:Semi-conductive material
Insulation: XLPE (Cross-Linked Polyethylene)
Outer Semi-Conductive Layer:Semi-conductive material
Screen:Copper wires
Sheath:PE (Polyethylene)
Sheath Colour: Black
APPLICATION
Medium voltage cables for distribution networks; also for connection to generation units and plant and process connection. For installation in ground, in water outdoors, indoors and in cable ducts for power stations, industry, and distribution networks.
CHARACTERISTICS
Voltage Rating Uo/U (Um) 6/10 (12)kV
Temperature Rating
-20°C to +90°C
Minimum Bending Radius
15 x overall diameter
CONSTRUCTION
Conductor:Class 2 stranded copper conductor
Inner Semi-Conductive Layer:Semi-conductive material
Insulation: XLPE (Cross-Linked Polyethylene)
Outer Semi-Conductive Layer:Semi-conductive material
Screen:Copper wires
Sheath:PE (Polyethylene)
Sheath Colour: Black
DIMENSIONS | |||||||||
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm² | NOMINAL OVERALL DIAMETER mm | NOMINAL WEIGHT kg/km | ||||||
Conductor | Copper Wire Screen | ||||||||
1 | 35 | 16 | 28 | 820 | |||||
1 | 50 | 16 | 29 | 960 | |||||
1 | 70 | 16 | 31 | 1150 | |||||
1 | 95 | 16 | 32 | 1450 | |||||
1 | 120 | 16 | 34 | 1700 | |||||
1 | 150 | 25 | 35 | 2000 | |||||
1 | 185 | 25 | 37 | 2350 | |||||
1 | 240 | 25 | 39 | 2900 | |||||
1 | 300 | 25 | 41 | 3550 | |||||
1 | 400 | 35 | 45 | 4500 | |||||
1 | 500 | 35 | 48 | 5550 |
ELECTRICAL CHARACTERISTICS | ||||||||||
NOMINAL CROSS SECTIONAL AREA mm² | CURRENT CARRYING CAPACITY IN TREFOIL Amps | |||||||||
Conductor | Copper Wire Screen | In Ground | In Air | |||||||
35 | 16 | 187 | 197 | |||||||
50 | 16 | 220 | 236 | |||||||
70 | 16 | 269 | 292 | |||||||
95 | 16 | 320 | 358 | |||||||
120 | 16 | 363 | 413 | |||||||
150 | 25 | 405 | 468 | |||||||
185 | 25 | 456 | 535 | |||||||
240 | 25 | 526 | 631 | |||||||
300 | 25 | 591 | 722 | |||||||
400 | 35 | 662 | 827 | |||||||
500 | 35 | 744 | 949 |