CONSTRUCTION
Conductor:Class 2 Stranded Copper
Inner Semi-Conductive Layer: Semi-conductive Material
Insulation: XLPE (Cross-Linked Polyethylene)
Outer Semi-Conductive Layer: Semi-conductive Material
Screen: Copper Wires and Copper Tape
Sheath: LSZH (Low Smoke Zero Halogen)
APPLICATION
UV resistant Medium voltage cables for distribution networks; also for connection to generation units and plant and process connection. LSZH outer sheath allows internal and external installation including directly in ground and in cable ducts.
CHARACTERISTICS
Voltage Rating Uo/U (Um) 12/20 (24)kV
Temperature Rating
-15ºC to +90ºC
Permissible short-circuit temperature up to 5 sec: +250°C
Minimum Bending Radius
15 x overall diameter
CONSTRUCTION
Conductor:Class 2 Stranded Copper
Inner Semi-Conductive Layer: Semi-conductive Material
Insulation: XLPE (Cross-Linked Polyethylene)
Outer Semi-Conductive Layer: Semi-conductive Material
Screen: Copper Wires and Copper Tape
Sheath: LSZH (Low Smoke Zero Halogen)
DIMENSIONS | |||||||||
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm² | NOMINAL OVERALL DIAMETER mm | NOMINAL WEIGHT kg/km | ||||||
Conductor | Copper Wire Screen | ||||||||
1 | 35 | 16 | 27 | 1000 | |||||
1 | 50 | 16 | 28 | 1200 | |||||
1 | 70 | 16 | 30 | 1400 | |||||
1 | 95 | 16 | 32 | 1700 | |||||
1 | 120 | 16 | 33 | 1900 | |||||
1 | 150 | 25 | 35 | 2300 | |||||
1 | 185 | 25 | 36 | 2750 | |||||
1 | 240 | 25 | 38 | 3300 | |||||
1 | 300 | 25 | 41 | 4000 | |||||
1 | 400 | 35 | 43 | 4800 | |||||
1 | 500 | 35 | 46 | 6000 | |||||
1 | 630 | 35 | 51 | 7300 | |||||
3 | 35 | 16 | 52 | 3300 | |||||
3 | 50 | 16 | 55 | 3900 | |||||
3 | 70 | 16 | 60 | 4800 | |||||
3 | 95 | 16 | 63 | 5800 | |||||
3 | 120 | 16 | 66 | 6700 | |||||
3 | 150 | 25 | 70 | 8000 | |||||
3 | 185 | 25 | 73 | 9200 | |||||
3 | 240 | 25 | 80 | 11300 | |||||
3 | 300 | 25 | 84 | 13500 | |||||
3 | 400 | 35 | 90 | 16500 |
ELECTRICAL CHARACTERISTICS Single Core | ||||||||||
NOMINAL CROSS SECTIONAL AREA OF CONDUCTOR mm² | NOMINAL SHORT-CIRCUIT CURRENT FOR 1 SECOND OF CONDUCTOR kA | CONDUCTOR DC RESITANCE AT 20ºC Ohm/km | CONDUCTOR AC RESISTANCE BY MAX. TEMPERATURE Ohm/km | CURRENT CARRYING CAPACITY A | CONDUCTOR LOSSES IN THE GROUND kW/km | |||||
In Ground at 20ºC | In Air at 30ºC | |||||||||
35 | 5.01 | 0.524 | 0.670 | 213 | 233 | 30.40 | ||||
50 | 7.15 | 0.387 | 0.497 | 250 | 279 | 31.06 | ||||
70 | 10.01 | 0.268 | 0.344 | 304 | 347 | 31.79 | ||||
95 | 13.59 | 0.193 | 0.248 | 361 | 420 | 32.32 | ||||
120 | 17.16 | 0.153 | 0.196 | 407 | 483 | 32.47 | ||||
150 | 21.45 | 0.124 | 0.160 | 445 | 540 | 31.68 | ||||
185 | 26.46 | 0.099 | 0.128 | 498 | 614 | 31.74 | ||||
240 | 34.32 | 0.0754 | 0.0980 | 569 | 718 | 31.73 | ||||
300 | 42.90 | 0.0601 | 0.0800 | 633 | 813 | 32.06 | ||||
400 | 57.20 | 0.0470 | 0.0640 | 686 | 904 | 30.12 | ||||
500 | 71.50 | 0.0366 | 0.0510 | 756 | 1011 | 29.15 | ||||
630 | 90.09 | 0.0283 | 0.0420 | 848 | 1160 | 30.20 |
ELECTRICAL CHARACTERISTICS Multi Core | ||||||||||
NOMINAL CROSS SECTIONAL AREA OF CONDUCTOR mm² | NOMINAL SHORT-CIRCUIT CURRENT FOR 1 SECOND OF CONDUCTOR kA | CONDUCTOR DC RESITANCE AT 20ºC Ohm/km | CONDUCTOR AC RESISTANCE BY MAX. TEMPERATURE Ohm/km | CURRENT CARRYING CAPACITY A | CONDUCTOR LOSSES IN THE GROUND kW/km | |||||
In Ground at 20ºC | In Air at 30ºC | |||||||||
35 | 5.01 | 0.524 | 0.670 | 178 | 173 | 63.68 | ||||
50 | 7.15 | 0.387 | 0.497 | 210 | 206 | 65.75 | ||||
70 | 10.01 | 0.286 | 0.344 | 256 | 257 | 67.63 | ||||
95 | 13.59 | 0.193 | 0.248 | 307 | 313 | 70.12 | ||||
120 | 17.16 | 0.153 | 0.196 | 349 | 360 | 71.62 | ||||
150 | 21.45 | 0.124 | 0.160 | 392 | 410 | 73.76 | ||||
185 | 26.46 | 0.099 | 0.128 | 443 | 469 | 75.36 | ||||
240 | 34.32 | 0.0754 | 0.0980 | 513 | 553 | 77.37 | ||||
300 | 42.90 | 0.0601 | 0.0800 | 576 | 635 | 79.63 | ||||
400 | 57.20 | 0.0470 | 0.0640 | 650 | 731 | 81.12 | ||||
Air ambient temperature: 30ºC Ground ambient temperature: 20ºC Conductor operating temperature: 90ºC Depth of duct: 0.7m Soil thermal resistivity: 1km/W |