N2XSY XLPE PVC - 12/20 (24)kV single copper core XLPE insulated with PVC oversheath

CONSTRUCTION

ConductorStranded copper

Inner Semi-Conductive LayerSemi-conductive material

InsulationXLPE (Cross-Linked Polyethylene)

Outer Semi-Conductive LayerSemi-conductive material

ScreenCopper wires

Sheath:  PVC (Polyvinyl Chloride)

STANDARDS

DIN VDE 0276-620, HD 620, IEC/EN 60228


Overview

APPLICATION

Medium voltage cables for distribution networks; also for connection to generation units and plant and process connection. To be laid directly in ground, outdoors, indoors and in cable ducts.

CHARACTERISTICS

Voltage Rating Uo/U (Um) 12/20 (24)kV

Temperature Rating

Fixed: -20°C to +90°C

Minimum Bending Radius

15 x overall diameter

CONSTRUCTION

ConductorStranded copper

Inner Semi-Conductive LayerSemi-conductive material

InsulationXLPE (Cross-Linked Polyethylene)

Outer Semi-Conductive LayerSemi-conductive material

ScreenCopper wires

Sheath:  PVC (Polyvinyl Chloride)

STANDARDS

DIN VDE 0276-620, HD 620, IEC/EN 60228


Parameter

DIMENSIONS
ELECTRICAL CHARACTERISTICS
DIMENSIONS
NO. OF CORESNOMINAL CROSS SECTIONAL AREA
mm²
MINIMUM OVERALL DIAMETER
mm
MAXIMUM OVERALL DIAMETER
mm
NOMINAL WEIGHT
kg/km
ConductorCopper Wire Screen
1351627321100
1501628331250
1701630351450
1951631361750
11201633382050
11502534392400
11852536412800
12402539443400
13002541464000
14003544494950
15003547526050
Expand More
ELECTRICAL CHARACTERISTICS
NOMINAL CROSS SECTIONAL AREA
mm²
CURRENT CARRYING CAPACITY
Amps
ConductorCopper Wire ScreenIn GroundIn Air
3516189200
5016222239
7016271297
9516323361
12016367416
15025409470
18525461538
24025532634
30025599724
40035671829
50035754953

Expand More