CONSTRUCTION
Conductor :Stranded copper conductor
Inner Semi-Conductive Layer: Semi-conductive material
Insulation: XLPE (Cross-Linked Polyethylene)
Outer Semi-Conductive Layer: Semi-conductive material
Screen: Copper wires
Sheath: PVC (Polyvinyl Chloride)
APPLICATION
Medium voltage cables for distribution networks; also for connection to generation units and plant and process connection. To be laid directly in ground, outdoors, indoors and in cable ducts.
CHARACTERISTICS
Voltage Rating Uo/U (Um) 18/30 (36)kV
Test Voltage
63kV
Temperature Rating
Fixed: -20°C to +90°C
Minimum Bending Radius
15 x overall diameter
CONSTRUCTION
Conductor :Stranded copper conductor
Inner Semi-Conductive Layer: Semi-conductive material
Insulation: XLPE (Cross-Linked Polyethylene)
Outer Semi-Conductive Layer: Semi-conductive material
Screen: Copper wires
Sheath: PVC (Polyvinyl Chloride)
DIMENSIONS | ||||||||||
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm² | MINIMUM OVERALL DIAMETER mm | MAXIMUM OVERALL DIAMETER mm | NOMINAL WEIGHT kg/km | ||||||
Conductor | Copper Wire Screen | |||||||||
1 | 50 | 16 | 33 | 38 | 1450 | |||||
1 | 70 | 16 | 35 | 40 | 1700 | |||||
1 | 95 | 16 | 36 | 41 | 2050 | |||||
1 | 120 | 16 | 38 | 43 | 2300 | |||||
1 | 150 | 25 | 39 | 44 | 2700 | |||||
1 | 185 | 25 | 41 | 46 | 3100 | |||||
1 | 240 | 25 | 43 | 48 | 3700 | |||||
1 | 300 | 25 | 46 | 51 | 4350 | |||||
1 | 400 | 35 | 49 | 54 | 5300 | |||||
1 | 500 | 35 | 52 | 57 | 6450 |
ELECTRICAL CHARACTERISTICS | |||||||||||
NOMINAL CROSS SECTIONAL AREA mm² | CURRENT CARRYING CAPACITY Amps | ||||||||||
Conductor | Copper Wire Screen | In Ground | In Air | ||||||||
50 | 16 | 225 | 241 | ||||||||
70 | 16 | 274 | 299 | ||||||||
95 | 16 | 327 | 363 | ||||||||
120 | 16 | 371 | 418 | ||||||||
150 | 25 | 414 | 472 | ||||||||
185 | 25 | 466 | 539 | ||||||||
240 | 25 | 539 | 635 | ||||||||
300 | 25 | 606 | 725 | ||||||||
400 | 35 | 680 | 831 | ||||||||
500 | 35 | 765 | 953 |