CONSTRUCTION
Conductor:Class 2 stranded copper conductor
Inner Semi-Conductive Layer:Semi-conductive material
Insulation:XLPE (Cross-Linked Polyethylene)
Outer Semi-Conductive Layer:Semi-conductive material
Tape 1:Water-swellable tape
Screen:Copper wires and copper tape
Tape 2: Aluminium foil tape tightly bonded to sheath
Outer Sheath: PE (Polyethylene)
APPLICATION
Medium voltage cables for distribution networks; also for connection to generation units and plant and process connection. For installation in ground, in water outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The water blocking tape avoids water propagation inside the cable.
CHARACTERISTICS
Voltage Rating Uo/U (Um) 6/10 (12)kV
Temperature Rating
-20°C to +90°C
Minimum Bending Radius
15 x overall diameter
CONSTRUCTION
Conductor:Class 2 stranded copper conductor
Inner Semi-Conductive Layer:Semi-conductive material
Insulation:XLPE (Cross-Linked Polyethylene)
Outer Semi-Conductive Layer:Semi-conductive material
Tape 1:Water-swellable tape
Screen:Copper wires and copper tape
Tape 2: Aluminium foil tape tightly bonded to sheath
Outer Sheath: PE (Polyethylene)
DIMENSIONS | ||||||
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm² | NOMINAL OVERALL DIAMETER mm | NOMINAL WEIGHT kg/km | |||
Conductor | Copper Wire Screen | |||||
1 | 35 | 16 | 29 | 870 | ||
1 | 50 | 16 | 30 | 1050 | ||
1 | 70 | 16 | 32 | 1300 | ||
1 | 95 | 16 | 33 | 1550 | ||
1 | 120 | 16 | 35 | 1800 | ||
1 | 150 | 25 | 36 | 2100 | ||
1 | 185 | 25 | 38 | 2450 | ||
1 | 240 | 25 | 40 | 3000 | ||
1 | 300 | 25 | 42 | 3650 | ||
1 | 400 | 35 | 46 | 4600 | ||
1 | 500 | 35 | 49 | 5600 |