CONSTRUCTION
Conductor: Class 2 stranded copper
Inner Semi-Conductive Layer: Semi-conductive material
Insulation: XLPE (Cross-Linked Polyethylene)
Outer Semi-Conductive Layer: Semi-conductive material
Screen: Copper wires and copper tape
Tape: Water-swellable tape
Outer Sheath: HFFR (Halogen Free Flame Retardant) UV resistant
APPLICATION
A UV resistant medium voltage cables for distribution networks with additional waterblocking layer available as single core or three-core variants; also for connection to generation units and plant and process connection with Halogen Free materials.
CHARACTERISTICS
Voltage Rating Uo/U (Um) 12/20 (24)kV
Temperature Rating
-15°C to +90°C
Minimum Bending Radius
15 x overall diameter
CONSTRUCTION
Conductor: Class 2 stranded copper
Inner Semi-Conductive Layer: Semi-conductive material
Insulation: XLPE (Cross-Linked Polyethylene)
Outer Semi-Conductive Layer: Semi-conductive material
Screen: Copper wires and copper tape
Tape: Water-swellable tape
Outer Sheath: HFFR (Halogen Free Flame Retardant) UV resistant
DIMENSIONS | ||||||||||||
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm² | NOMINAL OVERALL DIAMETER mm | NOMINAL WEIGHT kg/km | |||||||||
Conductor | Copper Wire Screen | |||||||||||
1 | 35 | 16 | 27 | 1000 | ||||||||
1 | 50 | 16 | 28 | 1200 | ||||||||
1 | 70 | 16 | 30 | 1400 | ||||||||
1 | 95 | 16 | 32 | 1700 | ||||||||
1 | 120 | 16 | 33 | 1900 | ||||||||
1 | 150 | 25 | 35 | 2300 | ||||||||
1 | 185 | 25 | 36 | 2750 | ||||||||
1 | 240 | 25 | 38 | 3300 | ||||||||
1 | 300 | 25 | 41 | 4000 | ||||||||
1 | 400 | 35 | 43 | 4800 | ||||||||
1 | 500 | 35 | 46 | 6000 | ||||||||
1 | 630 | 35 | 51 | 7300 | ||||||||
3 | 35 | 16 | 53 | 3700 | ||||||||
3 | 50 | 16 | 56 | 4200 | ||||||||
3 | 70 | 16 | 61 | 5100 | ||||||||
3 | 95 | 16 | 64 | 6200 | ||||||||
3 | 120 | 16 | 67 | 7000 | ||||||||
3 | 150 | 25 | 72 | 8400 | ||||||||
3 | 185 | 25 | 75 | 9700 | ||||||||
3 | 240 | 25 | 81 | 11800 | ||||||||
3 | 300 | 25 | 86 | 14000 | ||||||||
3 | 400 | 35 | 92 | 17200 |
ELECTRICAL CHARACTERISTICS Single Core | |||||||||||||||
NOMINAL CROSS SECTIONAL AREA mm² | CONDUCTOR AC RESISTANCE BY MAX TEMP | CONDUCTOR DC RESISTANCE AT 20oC | CURRENT CARRYING CAPACITY IN TREFOIL Amps | CONDUCTOR LOSSES IN THE GROUND kW/km | |||||||||||
Conductor | In Ground | In Air | |||||||||||||
35 | 0.670 | 0.524 | 213 | 233 | 30.40 | ||||||||||
50 | 0.497 | 0.387 | 250 | 279 | 31.06 | ||||||||||
70 | 0.344 | 0.268 | 304 | 347 | 31.79 | ||||||||||
95 | 0.248 | 0.193 | 361 | 420 | 32.32 | ||||||||||
120 | 0.196 | 0.153 | 407 | 483 | 32.47 | ||||||||||
150 | 0.160 | 0.124 | 445 | 540 | 31.68 | ||||||||||
185 | 0.128 | 0.099 | 498 | 614 | 31.74 | ||||||||||
240 | 0.0980 | 0.0754 | 569 | 718 | 31.73 | ||||||||||
300 | 0.0800 | 0.0601 | 633 | 813 | 32.06 | ||||||||||
400 | 0.0640 | 0.0470 | 686 | 904 | 30.12 | ||||||||||
500 | 0.0510 | 0.0366 | 756 | 1011 | 29.15 | ||||||||||
630 | 0.0420 | 0.0283 | 848 | 1160 | 30.20 |
ELECTRICAL CHARACTERISTICS Multi Core | |||||||||||||||
NOMINAL CROSS SECTIONAL AREA mm² | CONDUCTOR AC RESISTANCE BY MAX TEMP | CONDUCTOR DC RESISTANCE AT 20oC | CURRENT CARRYING CAPACITY IN TREFOIL Amps | CONDUCTOR LOSSES IN THE GROUND kW/km | |||||||||||
Conductor | In Ground | In Air | |||||||||||||
35 | 0.670 | 0.524 | 178 | 173 | 63.68 | ||||||||||
50 | 0.497 | 0.387 | 210 | 206 | 65.75 | ||||||||||
70 | 0.344 | 0.268 | 256 | 257 | 67.63 | ||||||||||
95 | 0.248 | 0.193 | 307 | 313 | 70.12 | ||||||||||
120 | 0.196 | 0.153 | 349 | 360 | 71.62 | ||||||||||
150 | 0.160 | 0.124 | 392 | 410 | 73.76 | ||||||||||
185 | 0.128 | 0.099 | 443 | 469 | 75.36 | ||||||||||
240 | 0.0980 | 0.0754 | 513 | 553 | 77.37 | ||||||||||
300 | 0.0800 | 0.0601 | 576 | 635 | 79.63 | ||||||||||
400 | 0.0640 | 0.0470 | 650 | 731 | 81.12 | ||||||||||
Air ambient temperature: 30oC Ground ambient temperature: 20oC Conductor operating temperature: 90oC Depth of duct: 0.7m Soil thermal resistivity: 1km/W |