CONSTRUCTION
Conductor: Class 2 stranded aluminium conductor
Inner Semi-Conductive Layer: Semi-conductive material
Insulation: XLPE (Cross-Linked Polyethylene)
Outer Semi-Conductive Layer: Semi-conductive material
Screen: Copper wires
Sheath: PE (Polyethylene)
STANDARDS
DIN VDE 0276-620, HD 620, EN 60228, IEC 60502-2
APPLICATION
Medium voltage cables for distribution networks; also for connection to generation units and plant and process connection. To be laid directly in ground, outdoors, indoors and in cable ducts.
CHARACTERISTICS
Voltage Rating Uo/U (Um) 12/20 (24)kV
Temperature Rating
-20°C to +90°C
Minimum Bending Radius
15 x overall diameter
CONSTRUCTION
Conductor: Class 2 stranded aluminium conductor
Inner Semi-Conductive Layer: Semi-conductive material
Insulation: XLPE (Cross-Linked Polyethylene)
Outer Semi-Conductive Layer: Semi-conductive material
Screen: Copper wires
Sheath: PE (Polyethylene)
STANDARDS
DIN VDE 0276-620, HD 620, EN 60228, IEC 60502-2
DIMENSIONS | ||||||||
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm² | NOMINAL OVERALL DIAMETER mm | NOMINAL WEIGHT kg/km | |||||
Conductor | Copper Wire Screen | |||||||
1 | 50 | 16 | 33 | 820 | ||||
1 | 70 | 16 | 35 | 930 | ||||
1 | 95 | 16 | 36 | 1050 | ||||
1 | 120 | 16 | 38 | 1150 | ||||
1 | 150 | 25 | 39 | 1350 | ||||
1 | 185 | 25 | 41 | 1500 | ||||
1 | 240 | 25 | 44 | 1750 | ||||
1 | 300 | 25 | 46 | 2000 | ||||
1 | 400 | 35 | 49 | 2350 |
ELECTRICAL CHARACTERISTICS | |||||||||
NOMINAL CROSS SECTIONAL AREA mm² | CURRENT CARRYING CAPACITY Amps | ||||||||
Conductor | Copper Wire Screen | In Ground | In Air | ||||||
50 | 16 | 172 | 185 | ||||||
70 | 16 | 210 | 231 | ||||||
95 | 16 | 251 | 280 | ||||||
120 | 16 | 285 | 323 | ||||||
150 | 25 | 319 | 366 | ||||||
185 | 25 | 361 | 420 | ||||||
240 | 25 | 417 | 496 | ||||||
300 | 25 | 471 | 569 | ||||||
400 | 35 | 535 | 660 |