CONSTRUCTION
Conductor: Class 2 stranded aluminium conductor
Inner Semi-Conductive Layer: Semi-conductive material
Insulation: XLPE (Cross-Linked Polyethylene)
Outer Semi-Conductive Layer: Semi-conductive material
Screen: Copper wires
Sheath: PE (Polyethylene)
STANDARDS
DIN VDE 0276-620, HD 620, EN 60228, IEC 60502-2
APPLICATION
Medium voltage cables for distribution networks; also for connection to generation units and plant and process connection. To be laid directly in ground, outdoors, indoors and in cable ducts.
CHARACTERISTICS
Voltage Rating Uo/U (Um) 18/30 (36)kV
Temperature Rating
-20°C to +90°C
Minimum Bending Radius: 15 x overall diameter
CONSTRUCTION
Conductor: Class 2 stranded aluminium conductor
Inner Semi-Conductive Layer: Semi-conductive material
Insulation: XLPE (Cross-Linked Polyethylene)
Outer Semi-Conductive Layer: Semi-conductive material
Screen: Copper wires
Sheath: PE (Polyethylene)
STANDARDS
DIN VDE 0276-620, HD 620, EN 60228, IEC 60502-2
DIMENSIONS | ||||||||
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm² | NOMINAL OVERALL DIAMETER mm | NOMINAL WEIGHT kg/km | |||||
Conductor | Copper Wire Screen | |||||||
1 | 50 | 16 | 38 | 1100 | ||||
1 | 70 | 16 | 40 | 1200 | ||||
1 | 95 | 16 | 41 | 1350 | ||||
1 | 120 | 16 | 43 | 1450 | ||||
1 | 150 | 25 | 44 | 1700 | ||||
1 | 185 | 25 | 46 | 1850 | ||||
1 | 240 | 25 | 48 | 2050 | ||||
1 | 300 | 25 | 51 | 2350 | ||||
1 | 400 | 35 | 54 | 2800 |
ELECTRICAL CHARACTERISTICS | |||||||||
NOMINAL CROSS SECTIONAL AREA mm² | CURRENT CARRYING CAPACITY Amps | ||||||||
Conductor | Copper Wire Screen | In Ground | In Air | ||||||
50 | 16 | 174 | 187 | ||||||
70 | 16 | 213 | 232 | ||||||
95 | 16 | 254 | 282 | ||||||
120 | 16 | 289 | 325 | ||||||
150 | 25 | 322 | 367 | ||||||
185 | 25 | 364 | 421 | ||||||
240 | 25 | 422 | 496 | ||||||
300 | 25 | 476 | 568 | ||||||
400 | 35 | 541 | 650 |