NYBY PVC 0.6/1kV Power Cable

CHARACTERISTICS

Voltage Rating Uo/U 0.6/1kV

Test Voltage

3.5kV

Temperature Rating

Maximum Operating: +70ºC Maximum Short-Circuit: +160°C

Minimum Bending Radius

12 x overall diameter


Overview

APPLICATION

The NYBY cable is suitable for installation indoors, in cable channels and in duct in ground in switchgear, power stations and industrial application, in harsh environments where a high level mechanical protection is required.

CONSTRUCTION

Conductor: Class 2 Stranded copper

Insulation: PVC (Polyvinyl chloride)

Filler: PVC (Polyvinyl chloride)

Armour: Double galvanized steel tape

Outer Sheath: PVC (Polyvinyl chloride)

STANDARDS

IEC 60502-1, VDE 0276-603, IS 1516.1


Parameter

NYBY PVC 0.6/1kV Power Cable DIMENSIONS
ELECTRICAL CHARACTERISTICS
NO. OF CORESNOMINAL CROSS SECTIONAL AREA
mm²
NOMINAL DIAMETER OF CONDUCTOR
mm
NOMINAL THICKNESS OF INSULATION
mm
NOMINAL THICKNESS OF OUTER SHEATH
mm
NOMINAL OVERALL DIAMETER
mm
NOMINAL WEIGHT
kg/km
21.51.370.81.2412273
22.51.760.81.2413319
242.2211.2415415
262.7211.2415469
2103.8511.2418639
2164.811.2420830
2255.851.21.24231154
2356.91.21.32251481
2508.11.41.4291923
2709.71.41.48332747
3103.8511.2419742
3164.811.2421985
3255.851.21.24241403
3356.91.21.32271818
3508.11.41.4312381
3709.71.41.48343179
39511.41.61.64394249
312012.651.61.72425128
315014.41.81.88486384
318515.7522.04527806
324018.22.22.25910156
316+104.811.24231280
325+165.851.21.24261777
335+166.91.21.32292167
350+258.11.41.4332853
370+359.71.41.56373770
395+5011.41.61.64424975
3120+7012.651.61.8466131
3150+7014.41.81.88507288
3185+9515.7522.04558960
3240+12018.22.22.26111377
41.51.50.81.2414338
42.51.760.81.2415391
442.2111.2417531
462.7211.2415539
4103.8511.24211016
4164.811.24231215
4255.851.21.32271900
4356.91.21.4302435
4508.11.41.48343173
4709.71.41.56384205
49511.41.61.72445594
412012.651.61.88476761
415014.41.81.96538335
418515.7522.125810146
424018.22.22.366613204
51.51.370.81.2414372
52.51.760.81.2416453
542.2111.2418620
562.7211.2419756
5103.8511.24231123
5164.811.24251559
5255.851.21.32302241
5356.91.21.4332883
5508.11.41.48373804
Expand More
ELECTRICAL CHARACTERISTICS
NOMINAL CROSS SECTIONAL AREA
mm2
CURRENT CARRYING CAPACITY
A
MAXIMUM CONDUCTOR RESISTANCE AT 20°C
Ω/km
IN CONDUITIN AIR
1.5322012.1
2.542277.41
454374.61
668483.08
1090661.83
16116891.15
251501180.727
351811430.524
502151760.387
702642240.268
1075601.83
1698801.15
251281060.727
351571310.524
501851590.387
702282020.268
952752440.193
1203132820.153
1503533240.124
1853993710.0991
2404644360.0754
16+1098801.15/1.83
25+161281060.727/1.15
35+161571310.524/1.15
50+251851590.387/0.727
70+352282020.268/0.524
95+502752440.193/0.387
120+703132820.153/0.268
150+703533240.124/0.268
185+953993710.0991/0.193
240+1204644360.0754/0.153

Expand More