A2XS(FL)2Y 1X120RM/16(12/20KV)
2025-06-26 15:31
2XS(FL)2Y / N2XS(FL)2Y A2XS(FL)2Y / NA2XS(FL)2Y A2XS(FL)2Y 1X120RM/16(12/20KV) describes a medium-voltage power cable.
A2XS(FL)2Y 1X120RM/16(12/20KV) It's a single-core, unarmored cable with an aluminum conductor, XLPE insulation, and a PE sheath. The cable is designed for a rated voltage of 12/20 kV (Um of 24 kV) and is longitudinally and radially water-blocked.
A2XS(FL)2Y:
This is the cable's type designation, indicating:
A: Aluminum conductor.
2XS: Cross-linked polyethylene (XLPE) insulation.
(FL): Longitudinal water-blocking with water swellable tape or layers.
2Y: Polyethylene (PE) outer sheath.
1X:
Single-core cable.
120RM/16:
120RM: Conductor cross-section of 120 mm², circular stranded.
16: Screen cross-section, likely copper wires and tape.
(12/20KV):
Rated voltage of 12/20 kV, which corresponds to a maximum system voltage of 24 kV.
This cable is suitable for installation in various environments, including underground, indoors, outdoors, and in cable ducts. Its water-blocking features make it suitable for use in areas where water ingress could be a concern.
2XS(FL)2Y / N2XS(FL)2Y A2XS(FL)2Y / NA2XS(FL)2Y
Uo/U - 6/10 kV, 12/20, 18/30kV, IEC 60502-2 / DIN VDE 0276-620
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants.
They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.
|
|
2XS( FL)2Y A2XS( FL)2Y
Uo/U - 3.6/6 kV, 8.7/15, 20/35 kV IEC 60502-2
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 3.6/6; 8.7/15; 20/35 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants.
They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter
|
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Need help?Email: info@qzcablegroup.com |