VOLTAGE: 0.6/1kV
CONDUCTOR: Class 1 Solid Aluminium; Class 2 stranded Copper
CONCENTRIC CONDUCTOR: Single Layer of Plain Copper Wires
NEUTRAL CONDUCTOR: Plain Copper Wires covered by a Polymeric Compound
EARTH CONTINUITY CONDUCTOR: Plain Copper wires
OUTER SHEATH: PVC (Polyvinyl Chloride); LSZH (Low Smoke Zero Halogen)
Application
Used by distribution network operators when providing the final connection to domestic properties. Also suitable for sub main distribution and particularly used within high-rise buildings and street lighting systems.
Standard
BS 7870
Construction
Type I Aluminum Concentric
Conductor : Class 1 solid aluminum conductor
Insulation: XLPE (Cross-Linked Polyethylene)
Concentric Conductor: Single layer of plain copper wires
Sheath: Black PVC (Polyvinyl Chloride)/Orange LSZH(Low Smoke Zero Halogen)
Type II Aluminum Split Concentric
Conductor : Class 1 solid aluminum conductor
Insulation: XLPE (Cross-Linked Polyethylene)
Neutral Conductor: Plain copper wires covered a blue polymeric compound
Earth Continuity Conductor: Plain copper wires
String Separator: Non-hygroscopic separator
Sheath: Black PVC (Polyvinyl Chloride)/Orange LSZH(Low Smoke Zero Halogen
Type III Copper Concentric
Conductor: Class 2 stranded copper conductor
Insulation: XLPE (Cross-Linked Polyethylene)
Concentric Conductor: Single layer of plain copper wires
Sheath: Black PVC (Polyvinyl Chloride)/ LSZH(Low Smoke Zero Halogen
Type IV Copper Split Concentric
Conductor : Class 2 stranded copper conductor
Insulation: XLPE (Cross-Linked Polyethylene)
Neutral Conductor: Plain copper wires covered a blue polymeric compound
Earth Continuity Conductor: Plain copper wires
String Separator: Non-hygroscopic separator
Sheath: Black Black PVC (Polyvinyl Chloride)/LSZH(Low Smoke Zero Halogen)
Type I Aluminum Concentric
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA | NOMINAL OVERALL DIAMETER | NOMINAL WEIGHT | MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20°C | MAXIMUM DC RESISTANCE OF CONCENTRIC CONDUCTOR AT 20°C | CURRENT CARRYING CAPACITY Amps | ||
mm2 | mm | kg/km | ohms/km | ohms/km | In Air | Clipped Direct | Enclosed in Conduit on a Wall | |
1 | 25 | 13 | 300 | 1.2 | 1.3 | 127 | 119 | 105 |
1 | 35 | 14 | 390 | 0.868 | 0.91 | 158 | 147 | 128 |
3 | 25 | 23 | 650 | 1.2 | 1.3 | 97 | 90 | 84 |
3 | 35 | 25 | 820 | 0.868 | 0.91 | 120 | 112 | 103 |
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA | NOMINAL OVERALL DIAMETER | NOMINAL WEIGHT | MAXIMUM DC RESISTANCE OF AT 20°C ohms/km | CURRENT CARRYING CAPACITY Amps | ||||
mm2 | mm | kg/km | CONDUCTOR | Neutral | Earth | In Air | Clipped Direct | Enclosed in Conduit on a Wall | |
1 | 25 | 15 | 490 | 1.2 | 1.2 | 1.2 | 127 | 119 | 105 |
1 | 35 | 16 | 610 | 0.868 | 0.76 | 1.2 | 158 | 147 | 128 |
3 | 25 | 23.5 | 830 | 1.2 | 1.2 | 1.2 | 97 | 90 | 84 |
3 | 35 | 26 | 1030 | 0.868 | 0.76 | 1.2 | 120 | 112 | 103 |
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA | NOMINAL OVERALL DIAMETER | NOMINAL WEIGHT | MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20°C | MAXIMUM DC RESISTANCE OF CONCENTRIC CONDUCTOR AT 20°C | CURRENT CARRYING CAPACITY Amps | ||
mm2 | mm | kg/km | ohms/km | ohms/km | In Air | Clipped Direct | Enclosed in Conduit on a Wall | |
1 | 4 | 8.5 | 140 | 4.61 | 4.8 | 42 | 41 | 37 |
1 | 16 | 12 | 370 | 1.15 | 1.2 | 100 | 99 | 88 |
1 | 25 | 14 | 550 | 0.727 | 0.76 | 135 | 130 | 117 |
Type IV Copper Split Concentric PARAMETER
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA | NOMINAL OVERALL DIAMETER | NOMINAL WEIGHT | MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20°C ohms/km | CURRENT CARRYING CAPACITY Amps | |||
mm2 | mm | kg/km | Metal-Coated Wires | Plain Wires | In Air | Clipped Direct | Enclosed in Conduit on a Wall | |
1 | 4 | 10 | 190 | 4.8 | 4.8 | 42 | 41 | 37 |
1 | 16 | 14 | 530 | 1.2 | 1.2 | 100 | 99 | 88 |
1 | 25 | 16 | 710 | 1.2 | 0.76 | 135 | 130 | 117 |
3 | 35 | 28.5 | 1900 | 0.76 | 0.55 | 129 | 120 | 110 |