Triplex-type aluminum conductors

Triplex-type aluminum conductors

Conductor de aluminio AA (1350-H19) soportado por un neutro desnudo. Aislado con polietileno (PE) o polietileno reticulado (XLPE).

Manufacturer in China

MOQ: 10KM

Send E-mail for Price List

Overview

CONSTRUCTION

Triplex type cables are made up of two insulated conductors and one bare conductor that can be AAC, ACSR or AAAC-6201-T81 twisted together; the phase and neutral conductors are made with concentrically stranded 1350-H19 or 6201-T81 aluminum alloy wires, respectively; the insulators are covered with a uniform layer of black polyethylene thermoplastic material (PE-Carbon Black) or cross-linked polyethylene (XLPE), also black, resistant to humidity, heat and sunlight; subsequently the two conductors are twisted together. Its form of packaging are reels in lengths according to the needs of the client.


APPLICATIONS

Triplex-type aluminum conductors are used for electrical connections supported by a bare neutral messenger from the secondary public network that passes through the sector to the meter or meter panel, in public lighting circuits and as a closed-type secondary network. This type of conductor can be used in dry and humid places, its maximum operating temperature is 75 °C or 90 °C (depending on the insulation used) and the service voltage is 0.3 kV for phase-neutral and 0.6 kV for phase-phase.


SPECIFICATIONS

• ASTM B230: Aluminum wires, alloy 1350-H19 for electrical purposes.

• ASTM B231: Type 1350-H19 stranded aluminum conductors in concentric layers.

• ASTM B786: Aluminum alloy 1350-H19 stranded conductors with 19 wires, unilay formation to be subsequently insulated.

• ASTM B232: Aluminum Stranded Conductors Reinforced with Steel (ACSR).

• ASTM B398: Aluminum Alloy Wires, 6201-T81 for electrical purposes.

• ASTM B399: Type 6201-T81 aluminum alloy stranded conductors in concentric layers.

• ANSI/NEMA WC-70 ICEA S-76-474: Power cables supported by a messenger neutral, with weather resistant insulation for 0.6 kV.

• NTE INEN 2 572: Pre-assembled cables supported by a load-bearing neutral, with weather-resistant extruded insulation up to 0.6 kV.

In addition to all the requirements of the National Electrical Code.triplex-2021.png

Parameter

AAC Neutral-Messenger

Code Word

Phase Conductor

Bare Neutral Messenger

Weight Per 1000 ft. (lbs.)

Allowable Ampacities+

Size (AWG)

Stranding

Covering Thickness (mils.)

Size (AWG)

Stranding

Rated Strength (lbs.)

POLY

XLP

POLY

XLP

Patella

6

7

45

6

7

563

103

103

70

85

Oyster

4

7

45

4

7

881

156

160

90

115

Clam

2

7

45

2

7

1350

232

238

120

150

Murex

1/0

7

60

1/0

7

1990

373

383

160

205

Purpura

1/0

19

60

1/0

7

1990

370

380

160

205

Nassa

2/0

7

60

2/0

7

2510

461

472

185

235

Trophon

2/0

19

60

2/0

7

2510

456

467

185

235

Melita

3/0

19

60

3/0

19

3310

562

562

215

275

Portunus

4/0

19

60

4/0

19

4020

696

696

245

315

Nannynose

336.4

19

80

336.4

19

6146

1118

1118

325

420


ACSR Neutral-Messenger

Code Word

Phase Conductor

Bare Neutral Messenger

Weight Per 1000 ft. (lbs.)

Allowable Ampacities+

Size (AWG)

Stranding

Covering Thickness (mils.)

Size (AWG)

Stranding

Rated Strength (lbs.)

POLY

XLP

POLY

XLP

Paludina

6

1

45

6

6/1

1190

109

110

70

85

Voluta

6

7

45

6

6/1

1190

116

118

70

85

Scallop

4

1

45

6

6/1

1190

143

146

90

115

Whelk

4

1

45

4

6/1

1860

165

169

90

115

Strombus

4

7

45

6

6/1

1190

156

160

90

115

Periwinkle

4

7

45

4

6/1

1860

172

176

90

115

Cockle

2

7

45

4

6/1

1860

227

233

120

150

Conch

2

7

45

2

6/1

2850

261

267

120

150

Janthina

1/0

7

60

2

6/1

2853

365

376

160

205

Neritina

1/0

7

60

1/0

6/1

4380

419

430

160

205

Ranella

1/0

19

60

2

6/1

2853

362

372

160

205

Cenia

1/0

19

60

1/0

6/1

4380

416

428

160

205

Cavolinia

2/0

7

60

1

6/1

3550

451

462

185

235

Runcina

2/0

7

60

2/0

6/1

5310

519

530

185

235

Clio

2/0

19

60

1

6/1

3550

437

444

185

235

Triton

2/0

19

60

2/0

6/1

5310

514

526

185

235

Aega

3/0

19

60

1/0

6/1

4380

549

559

215

275

Mursia

3/0

19

60

3/0

6/1

6620

626

633

215

275

Cerapus

4/0

19

60

2/0

6/1

5310

670

678

245

315

Zuzara

4/0

19

60

4/0

6/1

8350

777

785

245

315

Limpet

336.4

19

80

336.4

18/1

8680

1147

1161

325

420


6201 Alloy Neutral-Messenger

Code Word

Phase Conductor

Bare Neutral Messenger

Weight Per 1000 ft. (lbs.)

Allowable Ampacities+

Size (AWG)

Stranding

Covering Thickness (mils.)

ACSR Equivalent (AWG)

Stranding

Rated Strength (lbs.)

POLY

XLP

POLY

XLP

Minex

6

1

45

6

7

1110

101

102

70

85

Hippa

6

7

45

6

7

1110

105

107

70

85

Artemia

4

1

45

6

7

1110

132

134

90

115

Prawn

4

1

45

4

7

1760

152

154

90

115

Crab

4

7

45

6

7

1110

141

144

90

115

Barnacle

4

7

45

4

7

1760

157

160

90

115

Solaster

2

7

45

4

7

1760

212

216

120

150

Shrimp

2

7

45

2

7

2800

238

243

120

150

Sandcrab

1/0

7

60

2

7

2800

341

348

160

205

Gammarus

1/0

7

60

1/0

7

4460

384

390

160

205

Echinus

1/0

19

60

2

7

2800

336

342

160

205

Leda

1/0

19

60

1/0

7

4460

378

384

160

205

Dungenese

2/0

7

60

2/0

7

5390

474

481

185

235

Cyclops

2/0

19

60

2/0

7

5390

467

473

185

235

Fulgar

3/0

19

60

1/0

7

4460

518

525

215

275

Flustra

3/0

19

60

3/0

7

6790

588

596

215

275

Arca

4/0

19

60

2/0

7

5390

632

640

245

315

Lepas

4/0

19

60

4/0

7

8560

716

725

245

315

+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.

Inquiry
We respond quickly to any questions, inquiries, needs and feedback. If you have business needs or questions about our products, feel free to contact us.
WhatsApp

WhatsApp

WeChat

WeChat