Service Entrance Cable: Type SE, Style SER and SEU

Voltage: 600 Volt.

Conductor: Copper or Aluminum

Individual Conductors Rated XHHW-2 or THHN/THWN. 

Jacket and Individual Conductors Sunlight Resistant. 

Overview

Application

Type SE, service entrance cable is primarily used to convey power from the service drop to the meter base and from the meter base to the distribution panel board; however, the cable may be used in all applications where Type SE cable is permitted. SER may be used in wet or dry locations at temperatures not to exceed 90°C. Voltage rating is 600 volts.

 

COPPER SE SER SEU TYPE SERVICE ENTRANCE CABLE

copper seu ser.jpg

Construction

Constructed with sunlight resistant Type XHHW-2 conductors or Type THHN/THWN conductors.

Copper conductors are annealed (soft) copper.

Cable assembly plus reinforcement tape are jacketed with sunlight resistant gray polyvinyl chloride (PVC).

Available as 1 conductor with a concentric ground, 2 conductor with a round or concentric ground, or 3 conductor with a bare ground.

SE cable is jacketed with gray sunlight resistant polyvinyl chloride (PVC).

 

Standard

• ASTM- All applicable standards

• UL Standard 44 for XHHW-2 conductors

• UL Standard 83 for THHN/THWN conductors

• UL Standard 854

• Federal Specification A-A-59544

• National Electrical Code, NFPA 70. 2011 Edition

 

ALUMINUM SE SER SEU TYPE SERVICE ENTRANCE CABLE

ANTI-FRAUD COPPER ALUMINUM-SEU SER-1.jpgANTI-FRAUD COPPER ALUMINUM-SEU SER-2.jpg

Construction

Type SE cable is constructed with AA-8000 series aluminum alloy, compact stranded conductors.

The conductors are covered with a sunlight resistant Type XHHW-2 or Type THHN/THWN-2 insulation.

A reinforcement tape is wrapped around the conductors for added strength and conformity. A gray sunlight resistant polyvinyl chloride (PVC) outer jacket covers the entire assembly.

Style SEU cable has two phase conductors surrounded by a concentric neutral while the SER style has two, three or four phase conductors and a bare neutral.

 

Style SER Cable's phase conductors are identified by a colored stripe on the insulation.

3 conductor- Black and Black with Red Stripe

4 conductor- Black, Black with White Stripe, and Black with Red Stripe

5 conductor- Black, Black with White Stripe, Black with Red Stripe and Black with Blue Stripe

 

Standard

• ASTM- B-800 and B-801

• UL Standard 83 for THHN/THWN-2

• UL Standard 44 for XHHW-2

• Federal Specification A-A-59544

• National Electrical Code/NFPA 70, 2011 Edition

• RoHS

Parameter

COPPER SE SER SEU TYPE
ALUMINUM SE SER SEU TYPE
Size/ Construction (AWG)StrandingNominal O.D.(mils)Approximate Weight per 1000' (lbs)Allowable Ampacities+Standard Package
Phase & Neutral ConductorsEquipment Ground Conductor60° C75° C90° CDwelling
SER Copper  TWO CONDUCTOR WITH BARE GROUND (FORMERLY REFERRED TO AS "THREE CONDUCTOR")
8-8-87- -586231405055- -B
6-6-67- -669338556575- -B
4-4-47- -764498708595100B
3-3-37- -82961185100110110B
2-2-27- -89675295115130125B
1-1-119- -1021948110130150150C
1/0-1/0-1/019- -11141169125150170175C
2/0-2/0-2/019- -12091444145175195200C
3/0-3/0-3/019- -13171792165200225225C
4/0-4/0-4/019- -14382226195230260250C
SER Copper THREE CONDUCTOR WITH BARE GROUND (FORMERLY REFERRED TO AS "FOUR CONDUCTOR")
8-8-8-877645286405055- -B
6-6-6-677738424556575- -B
4-4-4-677844585708595100B
3-3-3-57791071985100110110B
2-2-2-47798488795115130125B
1-1-1-319711321117110130150150C
1/0-1/0-1/0-2191912351382125150170175C
2/0-2/0-2/0-1191913421713145175195200C
3/0-3/0-3/0-1/0191914622129165200225225C
4/0-4/0-4/0-2/0191915982650195230260250C
Table values reflect XHHW-2 conductors

Allowable ampacities shown are for general use as specified by the National Electrical Code, 2011 Edition, section 310.15 and 240.4(D).

Unless the is marked for use at higher temperaturesthe conductor ampacities shall be limited to the following per NEC 110.14(C) 60 ° C When terminated to equipment for circuits rated 100 amperes or less or marked for 14 – 1 AWG conductors.

75 ° C When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG . 90 ° C XHHW wet or Dry locations for ampacity adjustment purposes using NEC section 310.15

For dwelling ampacity use section 310.15(B)(7)
Package Code B- 1000' Reel

C- 500' Reel
Size/ Construction (AWG)StrandingNominal O.D.(mils)Approximate Weight per 1000' (lbs)Allowable Ampacities+Standard Package
Phase & Neutral ConductorsEquipment Ground Conductor60° C75° C90° CDwelling
SEU Copper ONE CONDUCTOR WITH A BARE CONCENTRIC GROUND (FORMALLY REFERRED TO AS "TWO CONDUCTOR")
8-878400144405055- -ABC
6-6712435208556575- -
4-4712506315708595- -C
2-271558048595115130- -
SEU Copper TWO CONDUCTOR WITH A BARE CONCENTRIC GROUND (FORMALLY REFERRED TO AS "THREE CONDUCTOR")
10-10-10112428 X 283127303030- -ABC
8-8-878587 X 380211405060- -ABC
6-6-6712659 X 416308556575- -BCE
4-4-4712815 X 506471708595100BCE
3-3-3712883 X 54858385100110110B
2-2-2715994 X 57871895115130125BD
1-1-119141093 X 664904110130150150B
1/0-1/0-1/019181179 X 7071123125150170175BC
2/0-2/0-2/019181283 X 7671379145175195200BC
3/0-3/0-3/019141429 X 8621712165200225225BD
4/0-4/0-4/019181541 X 9182146195230260250BC
SEU Copper TWO CONDUCTOR WITH A BARE CONCENTRIC GROUND (FORMALLY REFERRED TO AS "THREE CONDUCTOR") (REDUCED NEUTRAL)
6-6-878659 X 416281556575- -BC
4-4-6712790 X 481420708595100BC
3-3-5715843 X 50851585100110110BC
2-2-4712929 X 56363995115130125BC
Table values reflect XHHW-2 conductors

Allowable ampacities shown are for general use as specified by the National Electrical Code, 2011 Edition, section 310.15 and 240.4(D).

Unless the is marked for use at higher temperaturesthe conductor ampacities shall be limited to the following per NEC 110.14(C) 60 ° C When terminated to equipment for circuits rated 100 amperes or less or marked for 14 – 1 AWG conductors.

75 ° C When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG . 90 ° C XHHW wet or Dry locations for ampacity adjustment purposes using NEC section 310.15

For dwelling ampacity use section 310.15(B)(7)
Package Code: A- 250' Coil

B- 500' Reel

C- 1000' Reel

D- 100' Reel

E- 150' Coil
Expand More
ConductorStranding*Nominal O.D. (mils)Approx. Net Weight per 1000' (lbs)Standard Package
Size/Const. AWG or kcmilPhase Conductor & NeutralEquipment Ground Conductor
60° C75° C90° CDwelling
SER Aluminum Two Conductor With Bare Ground (Formerly referred to as "EZ-SE")
6-6-67-650405060-150B
4-4-47-745556575-203B
4-4-67-745556575-203B
2-2-27-8647590100100290B
2-2-47-8647590100100290B
2/0-2/0-112-1140115135150150527B
2/0-2/0-2/012-1140115135150150527B
4/0-4/0-2/019-1354150180205200784C
4/0-4/0-4/019-1354150180205200784C
SER Aluminum Three Conductor With Bare Ground (Formerly referred to as "Four Conductor")
8-8-8-811612304045-136B
6-6-6-677717405060-196B
4-4-4-677823556575-252B
2-2-2-4779567590100100359B
1-1-1-387107985100115110449C
1/0-1/0-1/0-21011168100120135125540C
2/0-2/0-2/0-11211264115135150150652C
3/0-3/0-3/0-1/01611371130155175175786C
4/0-4/0-4/0-2/01911496150180205200960C
250-250-250-3/022118391702052302251458C
SER Aluminum Four Conductor With Bare Ground (Formerly referred to as "Five Conductor")
2-2-2-2-46710597590100100452B 5
2/0-2/0-2/0-2/0-11211404115135150150827C
4/0-4/0-4/0-4/0-2/019116721501802052001228C
50-250-250-250-3/02211847170205230225
C
SEU Aluminum Two Conductor With Bare Concentric Ground (Formerly referred to as "Three Conductor")
6-6-678430 X 687405060-145H
4-4-6712499 X 800556575-198I
4-4-6715474 X 775556575-181I
2-2-2714569 X 9257590100100283I
2-2-4718554 X 9107590100100259I
2/0-2/0-2/01818736 X 1221115135150150514CJ
2/0-2/0-11814720 X 1205115135150150468CJ
4/0-4/0-4/01818878 X 1462150180205205765CL
4/0-4/0-2/01818835 X 1419150180205205691CL
Table values reflect XHHW-2 conductors. +Allowable Ampacities:
Allowable ampacities shown are for general use as specified by the National Electrical Code, 2011 Edition, Section 310.15.
60° C – When terminated to equipment for circuits rated 100 amperes or less or marked for 14 through 1 AWG conductors. See NEC Article 338.10(B)(4). 75° C – When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG. May not apply, see NEC Article 338.10(B)(4).
90° C – Wet or dry locations. For ampacity derating purposes.
Dwelling – For units, conductors shall be permitted at listed ampacities as 120/240-volt, 3-wire, single-phase services and feeders per NEC Article 310.15.
*For compact-stranded construction, the number of wires, as permitted by UL Standard 83, UL Standard 854, and ASTM B-801, may be reduced as follows:19-Wire Constructions – 18 Wires Minimum